Temperature changes in a low-profile, cross-ventilated building in the high plains

Date

2010-11-22

Journal Title

Journal ISSN

Volume Title

Publisher

Kansas State University. Agricultural Experiment Station and Cooperative Extension Service

Abstract

Performance of an evaporative cooling system was evaluated in the High Plains in a low-profile, cross-ventilated dairy facility housing 4,200 lactating cows. The temperature decrease across the 6-inch cellulose evaporative pad during the afternoon hours from July 15 to August 14, 2008, was 12.6°F. The temperature-humidity index was below 72 for 14 and 19 hours/day in pens near the outlet (exhaust fans) and inlet (near evaporative cooling pad), respectively, compared with 12 hours under ambient conditions. Throughout the study period, the evaporative cooling system decreased the number of hours that cows were housed in a heat stress environment irrespective of pen location in the building.

Description

Dairy Research, 2009 is known as Dairy Day, 2009

Keywords

Dairy, Dairy facilities, Heat stress, Temperature, Ventilation