Convective boiling of R-134a and R-123 on an enhanced tube bundle with standard pitch, RP-1316

dc.citation.doidoi:10.1080/10789669.2012.754308en_US
dc.citation.epage206en_US
dc.citation.issue2en_US
dc.citation.jtitleHVAC&R Researchen_US
dc.citation.spage193en_US
dc.citation.volume19en_US
dc.contributor.authorGorgy, Evraam
dc.contributor.authorEckels, Steven J.
dc.contributor.authoreideckelsen_US
dc.date.accessioned2013-04-05T16:20:11Z
dc.date.available2013-04-05T16:20:11Z
dc.date.issued2013-04-05
dc.date.published2013en_US
dc.description.abstractThe current paper presents the experimental investigation of the heat transfer performance of highly enhanced surfaced tube bundles. The two bundles studied are high pressure and low pressure TBII tubes for R-134a and R-123, respectively. The tube bundle is a staggered triangular arrangement with a tube pitch of (P/D 1.167). Twenty enhanced tubes were used in the bundle; the tube outer diameter and length are 19.05 mm (3/4 inch) and 1 m (39.36 inch), respectively. Three input variables were studied: heat flux (5-60 kW/m²), mass flux (15-55 kg/m².s), and quality (10-70%). The test saturation temperature was 4.44 °C for R-134a and 14.44 °C for R-123. The local heat transfer performance of the bundle is reported. A local method employing the Enthalpy Based Heat Transfer technique was implemented in the data reduction. Both tube bundles showed a strong dependency on heat flux as expected. The R-134a bundle showed a performance lower than that of pool boiling. The R-123 bundle showed a secondary dependency on quality. The quality effect becomes pronounced at high qualities and high average bundle heat load. In latter case enhanced tubes performance drops quickly and reaches that of a smooth tube.en_US
dc.identifier.urihttp://hdl.handle.net/2097/15454
dc.language.isoen_USen_US
dc.relation.urihttp://www.tandfonline.com/doi/full/10.1080/10789669.2012.754308en_US
dc.rightsThis is an electronic version of an article published in HVAC&R Research, 19(2), 193-206. HVAC&R Research is available online at: http://www.tandfonline.com/doi/full/10.1080/10789669.2012.754308en_US
dc.subjectTube bundlesen_US
dc.subjectHeat transferen_US
dc.subjectHeat fluxen_US
dc.titleConvective boiling of R-134a and R-123 on an enhanced tube bundle with standard pitch, RP-1316en_US
dc.typeArticle (author version)en_US

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
EckelsHVACRResearch2013.pdf
Size:
717.22 KB
Format:
Adobe Portable Document Format
Description:
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.62 KB
Format:
Item-specific license agreed upon to submission
Description: