A study of membrane properties on air conditioning performance

dc.contributor.authorBoyer, Elizabeth J.
dc.date.accessioned2013-05-08T12:52:05Z
dc.date.available2013-05-08T12:52:05Z
dc.date.graduationmonthMay
dc.date.issued2013-05-01
dc.date.published2013
dc.description.abstractEnergy consumption due to heating, ventilation, and air conditioning amounts to 10-20% of global electrical energy usage. Air conditioning alone uses one trillion kilowatt hours globally. This energy is required for the dehumidification of air in addition to its cooling. New membrane technologies have the potential to decrease air conditioning energy requirements by significant amounts. A membrane acts as a partial heat and mass exchanger in conjunction with a traditional air conditioning system to remove water content and reduce the cooling load. Membranes vary according to their properties and method of mass transport. Liquid membranes have high permeability and selectivity, dense membranes have high selectivity and low permeability, and porous membranes have low selectivity and high permeability. A theoretical model was created to observe how membrane properties affected the potential energy savings of such systems. The most influential properties were flow rate, water permeability and selectivity, membrane area and thickness, and the purge flow temperature. Other properties were determined to be minimally important such as outdoor temperature and humidity. The effect on energy savings in many cases was not a linear relationship but suggested an optimal value beyond which energy savings did not significantly increase. The best simulations showed electrical energy savings of 86-95%.
dc.description.advisorMary E. Rezac
dc.description.advisorMary E. Rezac
dc.description.degreeMaster of Science
dc.description.departmentDepartment of Chemical Engineering
dc.description.levelMasters
dc.identifier.urihttp://hdl.handle.net/2097/15758
dc.language.isoen_US
dc.publisherKansas State University
dc.rights© the author. This Item is protected by copyright and/or related rights. You are free to use this Item in any way that is permitted by the copyright and related rights legislation that applies to your use. For other uses you need to obtain permission from the rights-holder(s).
dc.rights.urihttp://rightsstatements.org/vocab/InC/1.0/
dc.subjectMembrane
dc.subjectAir conditioning
dc.subjectEnergy savings
dc.subject.umiChemical Engineering (0542)
dc.subject.umiEngineering (0537)
dc.subject.umiMechanical Engineering (0548)
dc.titleA study of membrane properties on air conditioning performance
dc.typeThesis

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
ElizabethBoyer2013.pdf
Size:
1.66 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.62 KB
Format:
Item-specific license agreed upon to submission
Description: