Local heat transfer coefficient for pool boiling of R-134a and R-123 on smooth and enhanced tubes

dc.citation.doi10.1016/j.ijheatmasstransfer.2012.02.012en_US
dc.citation.epage3028en_US
dc.citation.issue11-12en_US
dc.citation.jtitleInternational Journal of Heat and Mass Transferen_US
dc.citation.spage3021en_US
dc.citation.volume55en_US
dc.contributor.authorGorgy, Evraam
dc.contributor.authorEckels, Steven J.
dc.contributor.authoreideckelsen_US
dc.date.accessioned2012-07-10T19:35:08Z
dc.date.available2012-07-10T19:35:08Z
dc.date.issued2012-05-01
dc.date.published2012en_US
dc.description.abstractThe current paper presents experimental investigation of nucleate pool boiling of R-134a and R-123 on enhanced and smooth tubes. The enhanced tubes used were TBIIHP and TBIILP for R-134a and R-123, respectively. Pool boiling data were taken for smooth and enhanced tubes in a single tube test section. Data were taken at a saturation temperature of 4.44 °C. Each test tube had an outside diameter of 19.05 mm and a length of 1 m. The test section was water heated with an insert in the water passage. The insert allowed measurement of local water temperatures down the length of the test tube. Utilizing this instrumentation, local heat transfer coefficients were determined at five locations along the test tube. The heat flux range was 4-135 kW/m² for the TBIIHP tube and 5-60 kW/m² for the TBIILP tube. The resulting heat transfer coefficient range was 6,270-23,268 W/m².°C and 6,748-23,338 W/m².°C for both tubes, respectively. For smooth tube testing, the heat flux ranges were 7.3-130.7 kW/m² and 7.5-60.7 kW/m² for R-134a and R-123, respectively; with resulting heat transfer coefficient ranges of 1,798.9-11,379 kW/m².°C and 535.4-3,181.8 kW/m².°C. The study provided one of the widest heat flux ranges ever examined for these types of tubes and showed significant structure to the pool boiling curve that had not been traditionally observed. Additionally, this paper presented an investigation of enhanced tubes pool boiling models.en_US
dc.identifier.urihttp://hdl.handle.net/2097/14018
dc.relation.urihttp://doi.org/10.1016/j.ijheatmasstransfer.2012.02.012en_US
dc.subjectBoiling heat transferen_US
dc.subjectRefrigerants pool boilingen_US
dc.subjectFlooded evaporatorsen_US
dc.subjectEnhanced tubesen_US
dc.subjectLocal heat transfer coefficienten_US
dc.subjectEnthalpy based heat transfer analysisen_US
dc.titleLocal heat transfer coefficient for pool boiling of R-134a and R-123 on smooth and enhanced tubesen_US
dc.typeArticle (author version)en_US

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Eckels IntJHeatMassTrans 2012.pdf
Size:
354.7 KB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.62 KB
Format:
Item-specific license agreed upon to submission
Description: