Determining the effects of duct fittings on volumetric air flow measurements

dc.contributor.authorHickman, Craig
dc.date.accessioned2010-06-14T12:33:18Z
dc.date.available2010-06-14T12:33:18Z
dc.date.graduationmonthAugusten_US
dc.date.issued2010-06-14T12:33:18Z
dc.date.published2010en_US
dc.description.abstractThe purpose of the research was to quantify the influence of several duct disturbances on volumetric flow rate measurements and use these in developing guidelines for field technicians. This will assist the field technicians in making more accurate volumetric air flow measurements in rectangular ducts during a test and balance operation. Multiple duct sizes, fittings, probes, traverse algorithms, and locations upstream and downstream of the disturbances are used to compare a variety of situations. The two traverse algorithms used are the log-Tchebycheff and equal area methods. Two upstream and five downstream locations are tested for each duct configuration. Two air velocity probes are used for local velocity measurements on each traverse: a pitot-static probe and a hot wire anemometer. A nozzle bank and Air Flow Measurement Station are used as the flow measurement standards for comparison with each traverse. This paper discusses the setup and initial results of ASHRAE 1245-RP. Data collected subsequent to this thesis will complete the balance of results and will be collected and analyzed by other researchers. Results will be summarized and presented in a way which allows technicians to use it in the field for more accurate balancing results.en_US
dc.description.advisorB. Terry Becken_US
dc.description.degreeMaster of Scienceen_US
dc.description.departmentDepartment of Mechanical and Nuclear Engineeringen_US
dc.description.levelMastersen_US
dc.description.sponsorshipAmerican Society of Heating Refrigeration and Air-Conditioning Engineersen_US
dc.identifier.urihttp://hdl.handle.net/2097/4229
dc.language.isoen_USen_US
dc.publisherKansas State Universityen
dc.subjectHVACen_US
dc.subjectASHRAEen_US
dc.subjectDucten_US
dc.subjectAir flowen_US
dc.subject.umiEngineering, Mechanical (0548)en_US
dc.titleDetermining the effects of duct fittings on volumetric air flow measurementsen_US
dc.typeThesisen_US

Files

Original bundle
Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
CraigHickman2010.pdf
Size:
3.87 MB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.69 KB
Format:
Item-specific license agreed upon to submission
Description: