Convective boiling of R-134a and R-123 on an enhanced tube bundle with standard pitch, RP-1316

K-REx Repository

Show simple item record

dc.contributor.author Gorgy, Evraam
dc.contributor.author Eckels, Steven J.
dc.date.accessioned 2013-04-05T16:20:11Z
dc.date.available 2013-04-05T16:20:11Z
dc.date.issued 2013-04-05
dc.identifier.uri http://hdl.handle.net/2097/15454
dc.description.abstract The current paper presents the experimental investigation of the heat transfer performance of highly enhanced surfaced tube bundles. The two bundles studied are high pressure and low pressure TBII tubes for R-134a and R-123, respectively. The tube bundle is a staggered triangular arrangement with a tube pitch of (P/D 1.167). Twenty enhanced tubes were used in the bundle; the tube outer diameter and length are 19.05 mm (3/4 inch) and 1 m (39.36 inch), respectively. Three input variables were studied: heat flux (5-60 kW/m²), mass flux (15-55 kg/m².s), and quality (10-70%). The test saturation temperature was 4.44 °C for R-134a and 14.44 °C for R-123. The local heat transfer performance of the bundle is reported. A local method employing the Enthalpy Based Heat Transfer technique was implemented in the data reduction. Both tube bundles showed a strong dependency on heat flux as expected. The R-134a bundle showed a performance lower than that of pool boiling. The R-123 bundle showed a secondary dependency on quality. The quality effect becomes pronounced at high qualities and high average bundle heat load. In latter case enhanced tubes performance drops quickly and reaches that of a smooth tube. en_US
dc.language.iso en_US en_US
dc.relation.uri http://www.tandfonline.com/doi/full/10.1080/10789669.2012.754308 en_US
dc.rights This is an electronic version of an article published in HVAC&R Research, 19(2), 193-206. HVAC&R Research is available online at: http://www.tandfonline.com/doi/full/10.1080/10789669.2012.754308 en_US
dc.subject Tube bundles en_US
dc.subject Heat transfer en_US
dc.subject Heat flux en_US
dc.title Convective boiling of R-134a and R-123 on an enhanced tube bundle with standard pitch, RP-1316 en_US
dc.type Article (author version) en_US
dc.date.published 2013 en_US
dc.citation.doi doi:10.1080/10789669.2012.754308 en_US
dc.citation.epage 206 en_US
dc.citation.issue 2 en_US
dc.citation.jtitle HVAC&R Research en_US
dc.citation.spage 193 en_US
dc.citation.volume 19 en_US
dc.contributor.authoreid eckels en_US