| dc.description.abstract |
Emergency ratings have been introduced for operating transmission lines safely and supplying current capacity efficiently, as well as controlling load flow when occurring line faults. In this paper, short-term emergency ratings are calculated by using thermal equilibrium equation for bared conductors in double-circuit transmission lines. Overhead transmission lines installed in double-circuit have been extensively utilized worldwide to enhance power transmission. Such lines show various advantages in increasing transmission capacity and decreasing power loss as well as being operated flexibly during a contingency. Even when a fault occurs in one circuit, the healthy circuit can supply power continuously during emergency without outage. The utilization of such double-circuit transmission lines during normal and/or emergency operations is described. Maximum normal operating current based on fault duration, maximum allowable temperature of conductor, and thermal line ratings are evaluated. Several performances of dip/clearance affecting short-term emergency rating are also presented. |
en_US |
| dc.relation.uri |
http://www.tandfonline.com/doi/abs/10.1080/15325008.2012.658598 |
en_US |
| dc.rights |
This is an electronic version of an article published in Electric Power Components and Systems, 40(7), 729-740. Electric Power
Components and Systems is available online at: http://www.tandfonline.com/doi/abs/10.1080/15325008.2012.658598 |
en_US |
| dc.subject |
Double-circuit transmission lines |
en_US |
| dc.subject |
Short-term emergency rating |
en_US |
| dc.subject |
Thermal line rating |
en_US |
| dc.title |
Application and evaluation of short-term emergency ratings for double-circuit transmission lines |
en_US |
| dc.type |
Article (author version) |
en_US |
| dc.date.published |
2012 |
en_US |
| dc.citation.doi |
doi:10.1080/15325008.2012.658598 |
en_US |
| dc.citation.epage |
740 |
en_US |
| dc.citation.issue |
7 |
en_US |
| dc.citation.jtitle |
Electric Power Components and Systems |
en_US |
| dc.citation.spage |
729 |
en_US |
| dc.citation.volume |
40 |
en_US |
| dc.contributor.authoreid |
morcos |
en_US |